How to check and maintain the automatic fire water cannon? Because the fire water cannon requires continuous rotation, does it need to add lubricating oil frequently or inspect other components?

The automatic fire water cannon is capable of automatically spraying water to extinguish fires and is the backbone of firefighting equipment in the scene. Therefore, it is necessary to regularly check and ensure that the automatic fire water cannon is in normal operation. How to check and maintain it? Or how often should it be checked and maintained?

1.jpg

Standard regulations:

1. The control components of the fire water cannon should be checked daily, and the operating status and daily inspection registration form should be filled out.

2. The fire pump unit, valves, and pipeline network should be inspected once a month. During inspection, the water pump should be started to reach the rated pressure of the water cannon system.

3. Electric valves should be inspected every three months. During the inspection, the maintenance valve should be closed, the electric valve should be opened and closed, and the feedback signal should be checked. After the experiment is completed, open the maintenance valve.

4. The automatic fire monitor fire extinguishing system should be inspected every six months. During inspection, the stabilizing equipment should be turned off, and the water in the pipeline between the maintenance valve and the fire monitor should be drained before closing the maintenance valve. Ignite the test fire source, and the automatic fire extinguishing system should be able to issue a fire alarm signal; The fire monitor should start scanning and accurately aim at the fire source. The fire pump and electric valve operate normally, and the feedback signal display is normal; Other fire linkage equipment is operating normally, and the feedback signal display is normal. After the experiment and inspection are completed, open the maintenance valve. Fill the pipeline with water and ensure that the stabilizing equipment is working properly.

2.jpg

The inspection and maintenance of automatic fire water cannons is a part of daily fire inspection for an enterprise. The indicator lights on the control box flash normally during daily inspection. The fire pump is started every month, and the on/off valve of the electric valve is checked for normal operation every three months. The automatic fire water cannon is subjected to a water spray fire extinguishing test every six months.